Use PT Series Part Number Crossover Tool to convert from 100, 200, 300 and 615 Series transmitters to new PT Series transmitters.
Use PT Series Part Number Crossover Tool to convert from 100, 200, 300 and 615 Series transmitters to new PT Series transmitters.
Items |
/Asset/2000-Series-Digital-Indicator.jpg 2000-1-1-0 Current Input, 115/230 Vac, Smart System Indicator |
/Asset/2000-Series-Digital-Indicator.jpg 2000-1-1-1 Current Input, 115/230 Vac, Smart System Indicator with Dual Relay Card |
/Asset/2000-Series-Digital-Indicator.jpg 2000-1-1-156 Current Input, 115/230 Vac, Smart System Indicator with Dual Relay Card, Analog Output Card, and RS232 Card |
/Asset/2000-Series-Digital-Indicator.jpg 2000-1-1-5 Current Input, 115/230 Vac, Smart System Indicator with Analog Output Card |
/Asset/2000-Series-Digital-Indicator.jpg 2000-1-1-5-ENC1 Current Input, 115/230 Vac, Smart System Indicator with Analog Output Card and Black Steel National Electrical Manufacturers Association (NEMA) 4 Enclosure |
|||||
Description |
N/A
|
|||||||||
Type | N/A Digital Indicator | |||||||||
Series | N/A Single Input | |||||||||
Process Display | N/A 5 digit, 0.56" Red LED | |||||||||
Operating Temperature [Min] | N/A 0 ºC32 ºF | |||||||||
Operating Temperature [Max] | N/A 50 ºC122 ºF | |||||||||
Accuracy |
N/A
<0.03% of full scale, 64 ºF to 82 ºF (18 ºC to 50 ºC) <0.12% of full scale, 32 ºF to 122 ºF (0 ºC to 50 ºC) |
|||||||||
Storage Temperature | N/A -40 to 140 ºF-40 to 60 ºC | |||||||||
Effect | N/A ≤0.1 % | |||||||||
Full Scale Temperature | N/A 18 ºF10 ºC | |||||||||
Environmental Rating | N/A National Electrical Manufacturers Association (NEMA) 4, National Electrical Manufacturers Association (NEMA) 4X, Ingress Protection (IP65) (Front of Display Only) | |||||||||
Input Signals Current | N/A 4 to 20 mA | |||||||||
Alternating Current (AC) Voltage | N/A 115 V230 V | |||||||||
Direct Current (DC) Voltage | N/A | |||||||||
Direct Current (DC) Transmitter Power Supply Voltage | N/A 24 V | |||||||||
Key Pad | N/A 3 programmable function keys, 5 total | |||||||||
Power Requirement | N/A AC version 85 Vac to 250 Vac, 50/60 Hz, 15 VA, DC version 11 Vdc to 36 Vdc, 11 W | |||||||||
Electrical Connection | N/A Screw terminals at back of case | |||||||||
Memory | N/A Electrically Erasable Programmable Read-Only Memory (EEPROM) | |||||||||
Non-Condensing Humidity | N/A 85 % | |||||||||
Vibration | N/A 5 to 150 Hz2 g | |||||||||
Shock | N/A 25 g | |||||||||
Normal Rejection Mode | N/A 60 dB | |||||||||
Normal Rejection Mode Frequency | N/A 50 Hz60 Hz | |||||||||
Altitude | N/A Up to 2,000 m | |||||||||
Update Rate | N/A 200 ms | |||||||||
Selectable Filtering | N/A 0 to 25 s | |||||||||
Linearization | N/A 2 to 16 points, selectable | |||||||||
Reading [Min/Max] | N/A Captures and stores min/max measurement | |||||||||
User Inputs | N/A 3 programmable, 30 Vdc max. continuous | |||||||||
Sensor Excitation | N/A Built-in 24 Vdc | |||||||||
Totalizer Time Base | N/A Second, Minute, Hour or Day | |||||||||
Totalizer Time Batch | N/A Can accumulate from user input | |||||||||
Electromagnetic Rating | N/A European Conformity (CE) Compliant to Electromagnetic Compatibility (EMC) Norm European Standards (EN) 61326-1, Radio Frequency Interference (RFI), Electromagnetic Interference (EMI) and Electrostatic Discharge (ESD) Protection | |||||||||
Weight | N/A 10.4 oz | |||||||||
Warranty | N/A 2 yr | |||||||||
Optional Enclosures | N/A | N/A | N/A | N/A | N/A Black Painted Steel | |||||
Options | N/A Resistance Temperature Device (RTD), Thermocouple | |||||||||
Option Cards | N/A No Option Card | N/A Dual Relay Option Card | N/A Dual Relay Option Card | N/A Analog Output Option Card | N/A Analog Output Option Card | |||||
Limitations Which Apply Are |
N/A
These units must be operated within the catalogued environmental and application parameters. Determination of failure will be made by NOSHOK, Inc.'s equipment and personnel or a certified test facility specializing in this type of evaluation. In keeping with and for purposes of product and/or manufacturing process improvements, NOSHOK, Inc. reserves the right to make design changes without prior notice. |
|||||||||
Application |
N/A
|
|||||||||
Additional Information |
N/A
|
|||||||||
2000/2100 Series Smart System Intelligent Digital Indicator Option Cards |
N/A
|
N/A
|
N/A
|
N/A
|
N/A
|
|||||
AC to DC Retrofit Package |
N/A
|
|||||||||
NEMA 4 Enclosure - 1950 Series Digital Indicator |
N/A
|
|||||||||
|